前言:想要寫出一篇令人眼前一亮的文章嗎?我們特意為您整理了5篇機(jī)房防雷范文,相信會(huì)為您的寫作帶來(lái)幫助,發(fā)現(xiàn)更多的寫作思路和靈感。
關(guān)鍵詞:機(jī)房防雷;防雷裝置 ;防雷工程;等電位連接
Abstract: The computer because of its high efficiency, convenient, fast, the network system can realize the comprehensive data sharing, remote transmission, greatly enhance the work efficiency, so it is widely favored by people from all walks of life. Further to species diversity, rich in the form of computer room becomes an important part in intelligent building engineering, comprehensive attention gradually by the construction, design personnel. In order to improve the efficiency of computer application, realizes the equipment stability, reliable, safe operation must consider the system of computer room design, should be strictly in accordance with the standards of the existing. In this paper, how safe and reliable, advanced technology, design of lightning protection and lightning protection measures of economic reasonable grounding system is discussed.
Key words: lightning protection; lightning protection; lightning protection engineering; equipotential connection
中圖分類號(hào):TU856
1.現(xiàn)代防雷體系
現(xiàn)代防雷體系是從分析各種雷電威脅途徑著手,運(yùn)用防雷技術(shù),從外部到內(nèi)部,全方位、多層次地進(jìn)行攔截雷電的措施。
“躲”就是在建筑選址、時(shí)考慮防雷,躲開(kāi)多雷區(qū)或易落雷的地點(diǎn),是一條非常重要的經(jīng)濟(jì)有效的措施。
避雷針(帶,網(wǎng))、引下線和接地裝置是最基本且行之有效的建筑物外部防雷措施,沒(méi)有良好的、符合標(biāo)準(zhǔn)的避雷針(帶,網(wǎng))、引下線和接地裝置預(yù)先泄放雷電能量,任何其它防雷措施都從談起。
等電位連接,從物理學(xué)講,就是把各種金屬物之間用粗的導(dǎo)線焊接起來(lái)或把它們直接焊接起來(lái),以保證電位相等。完善的等電位連接,也可以消除因地電位驟然升高而產(chǎn)生的反擊現(xiàn)象。
傳導(dǎo)的作用是把閃電的巨大能量引導(dǎo)到大地耗散掉,當(dāng)然也可以研究其他方法來(lái)吸收、耗散它的能量,使它不能對(duì)被保護(hù)的對(duì)象產(chǎn)生破壞作用。
分流的作用是把沿導(dǎo)線傳入的過(guò)電壓波在避雷器處經(jīng)避雷器分流入地,也就是類似于把雷電流的所有入侵通道攔截了,而且不只是一級(jí)攔截,可以多級(jí)攔截。
接地是閃電能量的瀉放入地,雖然接地措施在防雷措施中是基礎(chǔ),如果沒(méi)有它,等電位連接、傳導(dǎo)、分流三個(gè)防雷措施就不可能達(dá)到預(yù)期的效果,接地是否妥當(dāng),是防雷技術(shù)上特別受重視的環(huán)節(jié),各種防雷規(guī)范都對(duì)接地措施做出了明確的規(guī)定。它又是防雷工程的重點(diǎn)和難點(diǎn),避雷裝置安全檢測(cè)的主要工作就是圍繞它
屏蔽就是用金屬網(wǎng)、箔管等導(dǎo)體把需要保護(hù)的對(duì)象包裹起來(lái),從物理意義上講,就是攔截閃電的脈沖電磁場(chǎng)從空間入侵的通道,力求“無(wú)隙可鉆”。
2.機(jī)房位置的選擇
由于計(jì)算機(jī)的特性對(duì)機(jī)房位址的選擇應(yīng)對(duì)設(shè)備運(yùn)輸、管線敷設(shè)、雷電感應(yīng)和結(jié)構(gòu)負(fù)載等問(wèn)題進(jìn)行綜合考慮和經(jīng)濟(jì)比較。首先電力供給要穩(wěn)定可靠,其次應(yīng)遠(yuǎn)離水災(zāi)火災(zāi)隱患區(qū)域、遠(yuǎn)離強(qiáng)震源和強(qiáng)噪音源,最后要避開(kāi)強(qiáng)電磁干擾,采用專用空調(diào)的主機(jī)房應(yīng)具備安裝室外機(jī)的建筑條件。
3.機(jī)房防雷接地系統(tǒng)設(shè)計(jì)
在計(jì)算機(jī)網(wǎng)絡(luò)系統(tǒng)中,為保證其穩(wěn)定可靠的工作、保護(hù)計(jì)算機(jī)網(wǎng)絡(luò)設(shè)備和人身安全,解決環(huán)境電磁干擾及靜電危害,需要一個(gè)良好的接地系統(tǒng)。計(jì)算機(jī)網(wǎng)絡(luò)的接地系統(tǒng)宜采用聯(lián)合接地方式,當(dāng)防雷接地與交流接地、直流工作接地、安全保護(hù)接地共用一組接地裝置時(shí),接地裝置的接地電阻值必須按接入設(shè)備中要求的最小值確定,接地電阻要求R<1Ω。機(jī)房的接地應(yīng)優(yōu)先考慮采用建筑物的自然接地網(wǎng)。聯(lián)合接地的優(yōu)點(diǎn)就是盡可能減少雷擊時(shí)相互連接設(shè)備間的電壓差,最大可能地實(shí)現(xiàn)等電位。機(jī)房的接地裝置包括機(jī)房?jī)?nèi)環(huán)形接地母排、設(shè)備接地線、及大樓基礎(chǔ)地網(wǎng),人工接地網(wǎng)
機(jī)房等電位連接主要是指將機(jī)房?jī)?nèi)所有金屬物體,包括電纜屏蔽層、金屬管道、金屬門窗、設(shè)備外殼等金屬構(gòu)件進(jìn)行電氣連接,放置重要設(shè)備的場(chǎng)所內(nèi)機(jī)房設(shè)備的功能等電位連接,在機(jī)房靜電地板下,沿墻體四周分別均布安裝環(huán)形接地母排,其截面為40mm×4mm的銅排母環(huán),距地面高約50-150mm,距墻800 mm,并每隔1000mm在銅排上鉆一個(gè)孔Φ10,將機(jī)房?jī)?nèi)的防雷地、工作交流地(N線)、靜電地、屏敝地、直流地、絕緣地、安全保護(hù)地等接地直接連接到環(huán)形接地母排上。機(jī)房環(huán)形接地母排與機(jī)房立柱內(nèi)主鋼筋至少兩處可靠焊接。
4.機(jī)房電源系統(tǒng)防雷保護(hù)設(shè)計(jì)
計(jì)算機(jī)房信息系統(tǒng)對(duì)雷電十分敏感,電子元器件耐受過(guò)電壓的能力很弱,任何雷電侵入途徑都可能造成損害,為了限制雷電感應(yīng),在被保護(hù)設(shè)備端口或附近裝設(shè)避雷器。在各種防雷措施的配置位置中,避雷器位于最后,是最后把關(guān)的。如果前面的其他各種防雷措施有所疏漏,則接在被保護(hù)設(shè)備端口或附近的避雷器還能截住殘余的、感應(yīng)的雷電電壓(電流),使設(shè)備受到最后的保護(hù)。所以避雷器對(duì)降低信息系統(tǒng)雷害概率、提高防雷可靠性有很好的、綜合性的作用。
對(duì)于低壓供電系統(tǒng),浪涌引起的瞬態(tài)過(guò)電壓保護(hù),采用分級(jí)保護(hù)的方式來(lái)完成。從大樓供電系統(tǒng)的進(jìn)入端開(kāi)始逐步進(jìn)行浪涌能量的釋放,對(duì)瞬態(tài)過(guò)電壓進(jìn)行分階段抑制。將雷電流引起的殘壓降低到設(shè)備承受的范圍內(nèi)。
4.1第一級(jí)電源防雷保護(hù)
根據(jù)國(guó)家有關(guān)低壓防雷的有關(guān)規(guī)定,外接金屬線路進(jìn)入建筑物之前必須埋地穿金屬管槽15米以上的距離進(jìn)入建筑物,且要在建筑物的線路進(jìn)入端加裝低壓避雷器。必須做到在電源的進(jìn)入端安裝低壓端的總電源防雷器,將由外部線路可能引入的雷擊高電壓引致大地泄放,以確保后接設(shè)備的安全。
對(duì)于機(jī)房電源一級(jí)電源防雷器,因在機(jī)房所在建筑物的總配電電源進(jìn)線端(三相四線)并聯(lián)安裝設(shè)I級(jí)試驗(yàn)的電涌保護(hù)器,其電壓保護(hù)水平值應(yīng)≦2.5kV,每一保護(hù)模式的沖擊電流值應(yīng)≧12.5kA,該防雷器在整個(gè)防雷系統(tǒng)中所起的根本作用是,當(dāng)發(fā)生強(qiáng)度很大的雷擊時(shí),通過(guò)第一級(jí)電源防雷器后的殘壓還比較高,仍可能大大超過(guò)被保護(hù)設(shè)備所能承受的最高耐壓值,在殘壓進(jìn)入機(jī)房之前將絕大部分電流泄放入地。
4.2第二級(jí)電源防雷保護(hù)
作為分級(jí)配電柜的次級(jí)防雷器,可將幾千伏的過(guò)電壓進(jìn)一步限制到2千伏以內(nèi),要求具有20KA以上的通流容量。防雷器并聯(lián)安裝在機(jī)房樓層分配電柜的電源進(jìn)線端處。可以對(duì)已經(jīng)經(jīng)過(guò)一級(jí)防雷器限制電壓的直擊雷、高強(qiáng)度感應(yīng)雷和一、二級(jí)間感應(yīng)雷實(shí)施泄放保護(hù)。要求第二級(jí)防雷器的線路安裝距離第一級(jí)防雷器10-15米,以使防雷器的動(dòng)作分級(jí)起效。
4.3第三級(jí)防雷保護(hù)
經(jīng)過(guò)一、二級(jí)防雷而進(jìn)入機(jī)房的雷擊殘壓仍將有千伏以上,這將對(duì)機(jī)房的后接設(shè)備造成很大的沖擊,并導(dǎo)致設(shè)備的損壞。作為第三級(jí)防雷器,要求有10KA以上的通流容量。防雷器并聯(lián)安裝在機(jī)房分配電柜的電源進(jìn)線端處。
機(jī)房?jī)?nèi)UPS電源為機(jī)房?jī)?nèi)的一些重要設(shè)備進(jìn)行供電保障,所以也需對(duì)UPS電源進(jìn)行感應(yīng)雷防護(hù),弱電系統(tǒng)的電源三級(jí)防雷采用最大放電電流達(dá)20KA電源避雷器,安裝在UPS主機(jī)前端;為了防止反擊,同時(shí)在各個(gè)UPS的輸出端安裝1組;因此需要2組電源避雷器對(duì)電源進(jìn)行其二級(jí)防雷。由于防雷器在泄放供電線路上高能量的雷電流時(shí),在防雷器兩端所呈現(xiàn)的殘壓仍然很高,仍可能大大超過(guò)被保護(hù)設(shè)備所能承受的最高耐壓值,因此通過(guò)三級(jí)防雷設(shè)備再次泄流而降低線路上的殘壓,進(jìn)一步降低真正到達(dá)設(shè)備供電端口的浪涌電壓值,使之小于設(shè)備耐壓值,從而在發(fā)生雷擊時(shí),使設(shè)備遭受損壞的可能性大大減小。
4.4末級(jí)電源防雷保護(hù)
這是系統(tǒng)防雷中最容易被忽視的地方,現(xiàn)代的電子設(shè)備都使用很多的集成電路和精密的元件,這些器件的擊穿電壓往往只是幾十伏,最大允許工作電源也只是mA級(jí)的,為了保護(hù)機(jī)房?jī)?nèi)重要電子設(shè)備(如交換機(jī)、其它重要設(shè)備等),選用較小通流量的插座電源防雷器,并聯(lián)插接在重要設(shè)備如服務(wù)器、交換矩陣、路由器等插座處,使整個(gè)機(jī)房的重要用電設(shè)備得到電源末級(jí)保護(hù),主要應(yīng)用在各個(gè)機(jī)房重要設(shè)備的用電插座上。最大負(fù)載電流可達(dá)到10KA。末級(jí)防雷器主要用于重要設(shè)備的前端,當(dāng)發(fā)生能量特別大的雷擊時(shí),感應(yīng)雷電流在經(jīng)過(guò)一、二、三級(jí)防雷器的泄放后,其殘壓仍然可能高于設(shè)備的最高耐壓值,重的設(shè)備的埠及內(nèi)部的高精度集成電路仍有可能被擊壞,經(jīng)過(guò)末級(jí)防雷器泄放殘余雷電流,設(shè)備的安全運(yùn)行就更為可靠了。
5.機(jī)房信號(hào)部分防護(hù)
在雷擊發(fā)生時(shí),產(chǎn)生巨大瞬變電磁場(chǎng),在1KM范圍內(nèi)的金屬環(huán)路,如網(wǎng)絡(luò)、信號(hào)及通訊金屬連線等都會(huì)感應(yīng)到雷擊,將會(huì)影響網(wǎng)絡(luò)、信號(hào)及通訊系統(tǒng)的正常運(yùn)行甚至徹底破壞系統(tǒng)。對(duì)于網(wǎng)絡(luò)、信號(hào)及通訊方面的防雷工作是較易被忽視的,往往是當(dāng)系統(tǒng)受到巨大破壞、資料損失慘重時(shí)才想到應(yīng)該做預(yù)先的防范。一般計(jì)算機(jī)房重要信息設(shè)備及對(duì)應(yīng)防雷設(shè)備主要為:
5.1、網(wǎng)絡(luò)主交換機(jī)與服務(wù)器設(shè)備是特別重要、特別敏感的設(shè)備,需要額外加以保護(hù)。
如果服務(wù)器與主交換機(jī)設(shè)備之間有一段較長(zhǎng)的距離,或靠近窗戶,容易感應(yīng)產(chǎn)生雷擊過(guò)壓,因此在服務(wù)器端口加裝RJ45-E100/4S信號(hào)防雷器。
5.2、根據(jù)通信設(shè)備的具體情況,主要考慮由室外引入的數(shù)據(jù)(語(yǔ)音)或視頻信號(hào)線路的防雷保護(hù)。避雷器主要串接在線路的兩端設(shè)備的接口處。
5.2.1、100M服務(wù)器輸入端口處安裝單口RJ45端口信號(hào)避雷器,以保護(hù)服務(wù)器。
5.2.2、24口網(wǎng)絡(luò)交換機(jī)串聯(lián)24口的RJ45端口信號(hào)避雷器,避免因雷擊感應(yīng)或電磁場(chǎng)干擾沿雙絞線竄入而毀壞設(shè)備。
5.2.3、在DDN專線接收設(shè)備上安裝單口RJ11端口信號(hào)避雷器,保護(hù)DDN專線上的設(shè)備。
5.2.4、在衛(wèi)星接收設(shè)備前端安裝同軸端口天饋線避雷器,以保護(hù)接收設(shè)備
【關(guān)鍵詞】通信基站;高鐵通信機(jī)械室;防雷地網(wǎng);保護(hù)
1.雷電的基本知識(shí)
1.1雷電的形成
雷電是伴有閃電和雷鳴的一種雄偉壯觀而又有點(diǎn)令人生畏的放電現(xiàn)象。雷電一般產(chǎn)生于對(duì)流發(fā)展旺盛的積雨云(雷云)中,因此常伴有強(qiáng)烈的陣風(fēng)和暴雨,有時(shí)還伴有冰雹和龍卷。積雨云頂部一般較高,可達(dá)20公里,云的上部常有冰晶。冰晶的凇附,水滴的破碎以及空氣對(duì)流等過(guò)程,使云中產(chǎn)生電荷。云中電荷的分布較復(fù)雜,但總體而言,云的上部以正電荷為主,下部以負(fù)電荷為主。因此,云的上、下部之間形成一個(gè)電位差。當(dāng)電位差達(dá)到一定程度后,就會(huì)產(chǎn)生放電,這就是我們常見(jiàn)的閃電現(xiàn)象。
雷云的產(chǎn)生必須具有以下三個(gè)基本條件:
a.空氣中應(yīng)有足夠的水蒸氣。
b.有使潮濕的空氣能夠開(kāi)始上升并開(kāi)始凝結(jié)為水珠的氣象條件或地形條件。
c.使氣流能強(qiáng)烈持續(xù)上升的物理?xiàng)l件。
雷云是在某些適當(dāng)氣象和地理?xiàng)l件下,由強(qiáng)大的潮熱氣流不斷上升進(jìn)入稀薄大氣冷凝的結(jié)果。
大多數(shù)雷電發(fā)電發(fā)生在云間或云內(nèi),只有小部分是對(duì)地發(fā)生的。在對(duì)地的雷電放電中,雷電的極性是指雷云下行到地的電荷的極性。根據(jù)放電電荷量進(jìn)行的多次統(tǒng)計(jì),90%左右的雷是負(fù)極性的。
1.2雷電的參數(shù)
1.2.1雷電流幅值的積累概率
雷電流幅值與雷云中電荷多少有關(guān),也與主放電形成過(guò)程有關(guān),是一個(gè)隨機(jī)變量,他與雷電活動(dòng)的頻繁程度相關(guān)。
1.2.2雷電通道的波阻抗Z
對(duì)雷電的研究,特別是雷電防護(hù)的研究,主要關(guān)心的是主放電通道的波阻抗。在主放電時(shí),雷電通道每米的電容和電感取C=14.2PF/m,L=1.84uH/m,算出雷電通道波阻抗Z=■=359(歐姆)。波速v=1/■=0.65C(C為光速)
注:C、L的估算值是以圓柱長(zhǎng)導(dǎo)體為模型。
2.鐵路通信機(jī)房及通信基站防雷設(shè)計(jì)
隨著鐵路建設(shè)的快速發(fā)展,鐵路客運(yùn)專線運(yùn)營(yíng)里程不斷增加,目前我國(guó)投入運(yùn)營(yíng)的高速鐵路已達(dá)到7055公里,我國(guó)高速鐵路運(yùn)營(yíng)里程居世界第一位,正在建設(shè)之中的高速鐵路有1萬(wàn)多公里。而CTCS-2及CTCS-3的運(yùn)用,全線通信基站及通信機(jī)房不斷增加。僅以滬杭客運(yùn)專線為例,滬杭高鐵由上海虹橋至杭州東站(杭州東站目前在建所以臨時(shí)引入杭州站)全長(zhǎng)153.5公里,正線2條,全程高架無(wú)隧道。沿線設(shè)7個(gè)車站、3個(gè)線路所、3個(gè)中繼站和45個(gè)基站。如此高密度的機(jī)房和基站對(duì)其防雷提出了新的要求。
2.1通信基站的綜合防雷設(shè)計(jì)
2.1.1基站簡(jiǎn)介
目前鐵路沿線使用的基站分為兩種類型,塔下基站和桿塔基站,而鐵路基站一般都建于郊外等空曠地區(qū),地處雷暴強(qiáng)度較強(qiáng)、雷暴日較多,遭遇雷擊事故概率較大。而且基站內(nèi)高集成高精密度設(shè)備對(duì)雷電的敏感度較強(qiáng)。雷擊事故成上升趨勢(shì),據(jù)不完全統(tǒng)計(jì),近年來(lái)遭遇雷擊的基站占到了總基站數(shù)的10%。影響了鐵路通信及運(yùn)輸安全。
2.1.2基站防雷措施存在的問(wèn)題
通過(guò)對(duì)通信基站的防雷設(shè)施檢測(cè).根據(jù)調(diào)查及用現(xiàn)實(shí)情況,經(jīng)過(guò)多方面的調(diào)研?;痉览状胧┩ǔ4嬖谝韵聠?wèn)題。
(1)基站鐵塔上的避雷針與通信天線的垂直、水平距離太近,沒(méi)有按照滾球法計(jì)算,接閃過(guò)程中,天饋線的電磁感應(yīng)電壓過(guò)高,損壞通信設(shè)備,鐵塔頂端至底端的過(guò)渡電阻I>0.03 歐姆,避雷針的接地電阻過(guò)大,不利于雷電流的泄流。
(2)基站天線鐵塔地網(wǎng)和機(jī)房地網(wǎng)沒(méi)有形成聯(lián)合接地。獨(dú)立鐵塔旁的機(jī)房或鐵塔下面的機(jī)房通信設(shè)備接地不規(guī)范,通信設(shè)備接地線從塔腳引入,沒(méi)有從地網(wǎng)處引入,存在地電位反擊。
(3)基站供電線路一般是采用架空引入,電力電纜金屬護(hù)套或鋼管兩端沒(méi)有就近可靠接地。配電屏中性線進(jìn)站后重復(fù)接地,室內(nèi)接地排與室外接地排沒(méi)有分開(kāi)設(shè)計(jì),沒(méi)有安裝適合的電涌保護(hù)器SPD,防止雷電波侵入。
(4)基站鐵塔高度≥60m.天饋線中間和進(jìn)入機(jī)房前都沒(méi)有接地。饋線與通信機(jī)端口未設(shè)置饋線SPD。光纖架空敷設(shè),光纖內(nèi)加強(qiáng)芯、光端機(jī)及通信設(shè)備未作接地處理,使光端機(jī)和設(shè)備損壞。
2.2通信機(jī)房防雷設(shè)計(jì)
通信機(jī)房的防雷主要通過(guò)屋頂避雷網(wǎng)、避雷帶和引下線、接地系統(tǒng)和機(jī)房屏蔽四塊來(lái)實(shí)現(xiàn)。
2.2.1作用
導(dǎo)流、屏蔽。
2.2.2材料
采用40mm×4mm熱鍍鋅扁鋼或不小于Φ8mm熱鍍鋅圓鋼,引下線與分線盤(柜)之間的距離不小于5m。引下線下端采用?準(zhǔn)50mm的絕緣管將引下線套起,防止雷擊時(shí),造成人員接觸電擊事故。絕緣管下端距地面距離30~50mm,絕緣管高度大于1.8m。
2.2.3設(shè)置
沿通信樓屋頂四周均勻設(shè)置4根以上,上端與避雷帶焊接連通,中間用膨脹螺栓固定在墻面上,引下線與墻面距離15mm。下端與地網(wǎng)焊接。引下線下端采用?準(zhǔn)50mm的絕緣管將引下線套起,防止雷擊時(shí),造成人員接觸電擊事故。絕緣管下端距地面距離30~50mm,絕緣管高度大于1.8m。
2.2.4工藝要求
所有扁鋼搭接處三面焊接,焊接長(zhǎng)度必須大于寬邊的2倍。焊點(diǎn)平滑無(wú)毛刺,并做防腐處理,防腐層應(yīng)在焊點(diǎn)四周延伸20-25mm,焊接處不得出現(xiàn)急彎(彎角不小于R90°),引下線與分線盤(柜)之間的距離不小于5m。與其它電氣線路距離大于1m。引下線的固定卡釘布置應(yīng)均勻牢固,間距宜小于2m。
2.3接地系統(tǒng)
2.3.1接地系統(tǒng)
通信設(shè)備應(yīng)設(shè)安全地線、屏蔽地線和防雷地線。通信設(shè)備的機(jī)架(柜)、控制臺(tái)、箱盒、梯子等應(yīng)設(shè)安全地線,交流電力牽引區(qū)段的電纜金屬護(hù)套應(yīng)設(shè)屏蔽地線,防雷保安器應(yīng)設(shè)防雷地線,安裝防靜電地板的機(jī)房應(yīng)設(shè)防靜電地線,微電子設(shè)備需要時(shí)可設(shè)置邏輯地線。上述地線均由共用接地系統(tǒng)的地網(wǎng)引出。
2.3.2地網(wǎng)
由各接地體、建筑物四周的環(huán)形接地裝置、基礎(chǔ)鋼筋構(gòu)成的接地體相互連接構(gòu)成。
【參考文獻(xiàn)】
[1]邊登程.通信基站的綜合防雷設(shè)計(jì)[期刊論文].黑龍江氣象,2009,(26).
【關(guān)鍵詞】通信機(jī)房 防雷措施 避雷裝置 等電位聯(lián)結(jié) 設(shè)備屏蔽
一、概述
隨著國(guó)民經(jīng)濟(jì)的快速發(fā)展,人們對(duì)于網(wǎng)絡(luò)通信質(zhì)量的要求越來(lái)越高,通信基站的數(shù)量不斷增加,類型也區(qū)域多樣化,大量通信機(jī)房得以建設(shè)。而信息化技術(shù)的快速發(fā)展,大量的微電子產(chǎn)品和設(shè)備應(yīng)用在通信基站內(nèi),來(lái)調(diào)節(jié)和控制移動(dòng)網(wǎng)絡(luò)通信信號(hào)的傳輸。微電子產(chǎn)品的廣泛應(yīng)用,提升通信設(shè)備性能的同時(shí),也大大降低了通信機(jī)房的耐壓能力,加大了通信機(jī)房在雷電防護(hù)問(wèn)題上的難度,尤其是安裝在電源主控室內(nèi)的通信設(shè)備,受到雷擊的概率更是大于其他機(jī)房。所以對(duì)雷電災(zāi)害的研究進(jìn)行深入研究來(lái)了解通信機(jī)房收雷電擊中而發(fā)生災(zāi)害的原理,對(duì)于通信機(jī)房的雷電防護(hù)問(wèn)題具有很大的現(xiàn)實(shí)意義。
二、雷電災(zāi)害形成以及對(duì)通信機(jī)房造成的災(zāi)害
雷電是自然界中常見(jiàn)的帶電云層放電現(xiàn)象。當(dāng)天空中有雷雨云層時(shí),云層會(huì)攜帶大量的電荷而產(chǎn)生靜電感應(yīng)作用。當(dāng)?shù)孛婺承┨厥馕矬w或者建筑物與帶電云層形成強(qiáng)電場(chǎng)而足以讓帶電云層進(jìn)行對(duì)地方放電時(shí)就形成了雷電現(xiàn)象。一般的,雷電現(xiàn)象對(duì)通信機(jī)房造成的破壞有直擊雷災(zāi)害和感應(yīng)雷災(zāi)害兩種形式。直擊雷是帶電云層直接放電而造成的破壞,這類雷電放電具有瞬發(fā)性,短時(shí)間內(nèi)形成高電壓并釋放大量的電流而對(duì)通信機(jī)房和通信設(shè)備造成強(qiáng)烈破壞。感應(yīng)雷是由于帶電云層與通信機(jī)房的信號(hào)傳輸線、設(shè)備連接線形成強(qiáng)電場(chǎng),強(qiáng)大的電磁感應(yīng)對(duì)通信設(shè)備中的微電子元件間接造成破壞的災(zāi)害現(xiàn)象。雖然沒(méi)有直擊雷造成的災(zāi)害嚴(yán)重,但是發(fā)生的概率卻很大,而且強(qiáng)電場(chǎng)形成的電磁感應(yīng)對(duì)微電子產(chǎn)品造成的過(guò)壓破壞會(huì)使通信設(shè)備產(chǎn)生故障而是通信機(jī)房癱瘓,對(duì)于整個(gè)通信網(wǎng)絡(luò)而言,造成的破壞也是不可估量的。所以感應(yīng)雷是通信機(jī)房主要防范的雷電災(zāi)害。
三、通信機(jī)房的防雷措施
通信機(jī)房的防雷措施主要以防止感應(yīng)雷為主,直擊雷主要通過(guò)安裝避雷裝置和浪涌保護(hù)器等保護(hù)裝置來(lái)降低雷電對(duì)通信機(jī)房?jī)?nèi)電源和通信設(shè)備等的危害。另一方面,在建設(shè)通信機(jī)房時(shí),要消滅機(jī)房?jī)?nèi)的防雷隱患等,確保將防雷工作做到最底層。
(一)安裝避雷裝置,減少電荷量
在通信機(jī)房上部安裝避雷裝置是通信機(jī)房的主動(dòng)防雷,通過(guò)避雷裝置,可以將通信機(jī)房上部的帶電云層在聚集電荷足夠多之前就對(duì)和帶電云層運(yùn)行形成通電回路而對(duì)帶電云層進(jìn)行放電,并將多余的電荷導(dǎo)入到大地,從而避免通信機(jī)房由于帶電云層電量過(guò)多而進(jìn)行放電造成的破壞。針對(duì)建筑物常見(jiàn)的避雷裝置有避雷針、避雷線、避雷器等,在建設(shè)通信機(jī)房時(shí),可以根據(jù)當(dāng)?shù)氐臍夂驐l件來(lái)選擇避雷裝置,或者多種裝置結(jié)合輔助使用以增強(qiáng)通信機(jī)房的防雷能力。此外,安裝在通信機(jī)房?jī)?nèi)的電源避雷器的引入線不宜過(guò)長(zhǎng),以避免在雷擊發(fā)生時(shí)由于引入線過(guò)長(zhǎng)而抬高雷電電位,同樣對(duì)通信設(shè)備造成過(guò)壓傷害。一般的,通信機(jī)房?jī)?nèi)的電源避雷器的火線引線應(yīng)該盡量短,加上和接地線總長(zhǎng)度應(yīng)盡量控制在5米以內(nèi),以確保雷電不會(huì)從交流引入線進(jìn)入通信機(jī)房。同時(shí),針對(duì)避雷裝置的安裝,針對(duì)通信機(jī)房的建筑、電源、通信設(shè)備等獨(dú)立、可靠接地,且相距一定距離,盡量避免保護(hù)地聯(lián)合使用,以避免使用同一接地線致使整體的防雷能力降低,防雷效果不佳。
(二)聯(lián)結(jié)機(jī)房等電位,消除電位差
針對(duì)通信機(jī)房防雷措施,雖然建筑、通信設(shè)備、電源等接地系統(tǒng)相互獨(dú)立,但是同類型內(nèi)部應(yīng)該進(jìn)行等電位聯(lián)結(jié)。當(dāng)通信機(jī)房遭受雷擊時(shí),如果通信建筑之間或者電子設(shè)備之間彼此接電線沒(méi)有等電位聯(lián)結(jié),那么彼此之間就會(huì)由于接地電阻而產(chǎn)生電位差,當(dāng)電位差足夠大時(shí),同樣會(huì)破壞通信機(jī)房的絕緣系統(tǒng),造成設(shè)備破壞。針對(duì)通信機(jī)房建筑之間的等電位聯(lián)結(jié),將建筑接地引下線與建筑柱內(nèi)鋼筋焊接在一起,從而使建筑接地形成上端與頂層混凝土鋼筋相焊接,地部與地網(wǎng)相焊接,從而形成籠式避雷網(wǎng),將雷電的高電流強(qiáng)電壓進(jìn)行分流均壓。同樣的,針對(duì)電子設(shè)備的等電位聯(lián)結(jié),需要將通信設(shè)備中的電氣、電子設(shè)備的金屬外殼、通信電纜外皮、設(shè)備機(jī)柜、各種浪涌保護(hù)器、安全保護(hù)器等接地端都應(yīng)該以最短的距離聯(lián)結(jié)起來(lái),以降低甚至消除電子設(shè)備內(nèi)部防雷系統(tǒng)的電位差。
(三)加強(qiáng)通信設(shè)備雷電防護(hù)
通信機(jī)房的雷電防護(hù)要確保通信設(shè)備的正常運(yùn)作,以保證通信網(wǎng)絡(luò)的正常運(yùn)行。通信設(shè)備的保護(hù)包括電源保護(hù)和設(shè)備屏蔽兩部分。針對(duì)電源的雷電防護(hù),需將避雷器加裝到通信機(jī)房總配電室的電纜內(nèi)芯兩段來(lái)進(jìn)行一級(jí)保護(hù),同時(shí)在通信機(jī)房每個(gè)樓層的電纜內(nèi)芯兩側(cè)加裝避雷器進(jìn)行二級(jí)防護(hù),最后在各種重要的通信設(shè)備以及UPS前段對(duì)地部分加裝避雷器作為三級(jí)保護(hù),最終確保侵入電源系統(tǒng)內(nèi)的雷電流通過(guò)分流技術(shù)將其泄入大地。通信設(shè)備的屏蔽的主要目的是避免雷電產(chǎn)生的電磁場(chǎng)對(duì)通信設(shè)備進(jìn)行干擾而擾亂通信網(wǎng)絡(luò)的正常運(yùn)轉(zhuǎn)。通信設(shè)備屏蔽包括空間屏蔽和線路屏蔽,線路屏蔽是對(duì)網(wǎng)絡(luò)信號(hào)線和電源線進(jìn)行屏蔽,此外還需對(duì)機(jī)房進(jìn)行屏蔽,將其內(nèi)部的金屬門、窗等以及防靜電專業(yè)地板進(jìn)行接地,以減少雷電場(chǎng)對(duì)通信設(shè)備的干擾。
四、總結(jié)
通信機(jī)房的雷電防護(hù)措施主要從預(yù)防雷電災(zāi)害的直擊雷和感應(yīng)雷兩方面入手,通過(guò)為通信機(jī)房建筑、通信設(shè)備、電源等進(jìn)行避雷設(shè)備安裝,以減少帶電云層放電時(shí)對(duì)通信機(jī)房造成的危害,同時(shí)通過(guò)內(nèi)部接地系統(tǒng)的等電位聯(lián)結(jié),降低甚至消除由于接地電阻產(chǎn)生的電位差,同時(shí)要加強(qiáng)通信設(shè)備的雷電防護(hù)工作,確保設(shè)備電源供應(yīng)正常,設(shè)備運(yùn)轉(zhuǎn)正常。通信機(jī)房的防雷工作要從細(xì)處入手,做到方方面面,一點(diǎn)疏忽就會(huì)造成整個(gè)防雷系統(tǒng)失效,所以我們要不斷努力,將通信機(jī)房的防雷工作做到細(xì)處,保證通信設(shè)備正常運(yùn)轉(zhuǎn),保證通信網(wǎng)絡(luò)正常提供服務(wù)。
參考文獻(xiàn):
[1]孫君厚,趙志國(guó),金兆華. 通信機(jī)房和設(shè)備的防雷技術(shù)與實(shí)踐研究[J]. 技術(shù)創(chuàng)新和應(yīng)用. 2012(15)
關(guān)鍵詞 廣播電視;發(fā)射機(jī)房;防雷問(wèn)題
中圖分類號(hào)G2
文獻(xiàn)標(biāo)識(shí)碼A
文章編號(hào)1674-6708(2016)156-0052-02
雷電是非常嚴(yán)重的一種自然災(zāi)害,其有著巨大的釋放能量和較短的放電時(shí)間,在雷電發(fā)生時(shí),會(huì)有上萬(wàn)安培的泄放電流,如果廣播電視機(jī)房沒(méi)有將相應(yīng)的防雷措施運(yùn)用過(guò)來(lái),就會(huì)帶來(lái)十分巨大的破壞,損壞到設(shè)備,中斷廣播電視信號(hào)等。因此,就需要采取一系列的防雷措施。
1 雷擊機(jī)房的主要方式
1.1 經(jīng)過(guò)架空管線侵入
現(xiàn)階段電視機(jī)房將有線網(wǎng)絡(luò)的架空管線給運(yùn)用過(guò)來(lái),這樣如果有雷電現(xiàn)象發(fā)生,就會(huì)有巨大的電場(chǎng)形成于較大的范圍內(nèi),因?yàn)樗诫妶?chǎng)為架空管線接近終端位置的主要成分,在電場(chǎng)突出物體上容易積聚感應(yīng)電荷,提升周圍電場(chǎng)強(qiáng)度,在放電作用下,很容易雷擊到架空管線的突出部分,進(jìn)而導(dǎo)致設(shè)備過(guò)電壓的發(fā)生,對(duì)廣電設(shè)備造成較為嚴(yán)重的損壞。同時(shí),雷云對(duì)地放電作用下,依然會(huì)有感應(yīng)過(guò)電壓產(chǎn)生于架空管線上,進(jìn)而嚴(yán)重?fù)p壞電源設(shè)備。
1.2 經(jīng)過(guò)發(fā)射鐵塔和天饋線侵入
一般來(lái)講,發(fā)射鐵塔具有70m~llOm左右的高度,雷電發(fā)生時(shí),鐵塔上的避雷針被雷電擊中,順著鐵塔,經(jīng)過(guò)接地設(shè)備向地下流入產(chǎn)生的電流,在較大程度上升高地網(wǎng)電位,增加了設(shè)備和機(jī)房地網(wǎng)之間的電位差,導(dǎo)致地電位反擊出現(xiàn),進(jìn)而嚴(yán)重?fù)p壞到設(shè)備。因?yàn)閷⑼S電纜作為天饋線,雷擊時(shí),會(huì)有較高的感應(yīng)電流產(chǎn)生,經(jīng)過(guò)天饋線,機(jī)房中進(jìn)入感應(yīng)電流,也會(huì)嚴(yán)重?fù)p壞到機(jī)房設(shè)備。
2 廣播電視發(fā)射機(jī)房防雷措施
2.1 天線防雷措施
為了促使廣播電視發(fā)射機(jī)房的安全得到保證,需要將避雷針安裝于天線塔頂,這樣可以有效放電于云層靜電荷,防雷作用也能充分發(fā)揮。同時(shí),要將避雷裝置安裝于天線上,裝置設(shè)置放射線,以便有效化解掉云層的電荷。一般來(lái)講,在天線基面絕緣體上設(shè)置放電球,按照l(shuí)OOmm的標(biāo)準(zhǔn)控制其直徑。防雷電保護(hù)器中,放電球發(fā)揮著較大的作用,通過(guò)運(yùn)用放電球,可以促使惡劣天氣狀況下,設(shè)備的正常工作不受影響。要平行放置兩種放電器,避免豎立放置。冬天時(shí)分,采取一些措施,避免被積雪所覆蓋。此外,在天線防雷系統(tǒng)接地中,則可以選擇有較小電阻的線纜,按照l(shuí)OOm的標(biāo)準(zhǔn)控制天線塔之間的距離,深度需要達(dá)到地下水層。為了將防雷電電流的作用給充分發(fā)揮出來(lái),可以將一個(gè)或者多個(gè)環(huán)加設(shè)于天線饋線部分,這樣能夠有低電感限制圈形成,還可以避免由同軸饋入電纜,而導(dǎo)致廣播電視發(fā)射機(jī)房中進(jìn)入電流,經(jīng)濟(jì)性較好。
2.2 電源防雷措施
電源是廣播電視發(fā)射機(jī)房設(shè)備的共同載體,如果損壞到了電源,就會(huì)導(dǎo)致雷電損壞到整個(gè)系統(tǒng),因此,需要充分重視電源避雷器的作用,但是依然需要將隔離變壓器安裝于關(guān)鍵設(shè)備終端。這樣可以避免通過(guò)電源,而導(dǎo)致廣播電視機(jī)器設(shè)備遭到雷電的損壞。一般可以將這些措施給運(yùn)用過(guò)來(lái),首先將架空地線架設(shè)于高壓線的進(jìn)線上,控制線長(zhǎng)度在lOOOm以上;將避雷針安裝于防雷區(qū)域;將避雷器安裝于進(jìn)電站處;結(jié)合電力系統(tǒng)規(guī)范要求,科學(xué)安置線路接地設(shè)施。避雷針的安裝,如果有直擊雷侵入天饋系統(tǒng),能夠向大地引入雷電產(chǎn)生的電流。一般利用不銹鋼或者鍍鋅鋼來(lái)制作避雷針,厚度控制在3mm以內(nèi),直徑控制為25mm~40mm以內(nèi),同時(shí),保護(hù)直徑應(yīng)該為1.5倍的高度。在防雷地網(wǎng)構(gòu)建中,中心選擇的是機(jī)房和鐵塔,之后將50cm左右的地溝給挖出來(lái),然后在地下釘入4根2m左右的鍍鋅角鐵釘,按照20m的標(biāo)準(zhǔn)控制其間距,并且焊接扁鐵,同時(shí)接地連接鐵塔和機(jī)房,并且防腐處理焊接口。
2.3 設(shè)備接地防雷措施
地線是重要的一種設(shè)備接地防雷措施,具體來(lái)講,地線就是將導(dǎo)線設(shè)置于廣播電視發(fā)射機(jī)房的發(fā)射機(jī)中,以便向大地有效引導(dǎo)雷電產(chǎn)生的電流。如果出現(xiàn)了過(guò)高的電壓,或者設(shè)備漏電等問(wèn)題,借助于地線,電流可以有效流向大地。因此,在電路中,十分重要的一個(gè)組成部分就是地線。通過(guò)接地和屏蔽措施的運(yùn)用,能夠有效防護(hù)雷電電磁干擾。在電路內(nèi)部,接地可以作為電位參考點(diǎn)而存在,借助于接地參考點(diǎn),能夠?qū)ζ渌娢挥行y(cè)量。接地也可以看作為一個(gè)連接,有效連接了大地。
2.4 加裝保護(hù)裝置
為了促使機(jī)房防雷能力得到提高,需要分類架空導(dǎo)線,然后借助于金屬管埋入地下,之后進(jìn)入機(jī)房,不能夠向機(jī)房直接引入架空導(dǎo)線。如果有較遠(yuǎn)的路程,需要將保護(hù)裝置加裝于電力線及電纜兩端。電力線和信號(hào)線分別屬于強(qiáng)電和弱電,如果走線時(shí)混合電力線和信號(hào)線,將會(huì)造成不利的影響。因此,在實(shí)踐中,需要在地線上焊接金屬管的兩端,同時(shí)防腐處理焊點(diǎn)。其他設(shè)備則需要嚴(yán)格依據(jù)相應(yīng)的安裝要求,連接系統(tǒng)與接地匯流排,之后連接室內(nèi)接地排。機(jī)房中,一般是從室內(nèi)地線排中引入設(shè)備的電源接地線,并且互相獨(dú)立保護(hù)地,之后連接接地匯流排,不能夠與引線共用。
2.5 預(yù)留接地孔
為了提升防雷水平,施工過(guò)程中,需要將接地孔預(yù)留于鐵塔頂部天線平臺(tái)、鐵塔中間及鐵塔基礎(chǔ)上,在接地點(diǎn)方面,可以將塔身螺栓發(fā)展為加長(zhǎng)型螺栓。因?yàn)殍F塔具有較高的高度,因此,如果鐵塔相鄰兩個(gè)接地點(diǎn)的距離在60m以內(nèi)時(shí),就需要將一個(gè)接地點(diǎn)增設(shè)于兩個(gè)結(jié)點(diǎn)之間;同時(shí),為了促使雷電流得到分散,需要對(duì)連接點(diǎn)的分散性和數(shù)量嚴(yán)格控制,并且每隔5m,就需要相互連接機(jī)房地網(wǎng)及鐵塔地網(wǎng),相互連通需要保證在2處以上。為了避免雷擊危害,機(jī)房需要全部焊接信號(hào)接收天線,之后將避雷針安裝于天線豎桿上,要對(duì)避雷針的高度嚴(yán)格控制,以便對(duì)天線設(shè)備有效的保護(hù)。
關(guān)鍵詞:有線電視前端機(jī)房 防雷 接地
中圖分類號(hào):TN948.6 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1674-098X(2014)09(b)-0042-01
1 雷電危害的特點(diǎn)
雷擊一般分為直擊雷和感應(yīng)雷。直擊雷是指被雷電直接擊中,其危害較大,但一般可通過(guò)架設(shè)避雷針和防雷網(wǎng)來(lái)進(jìn)行防護(hù)。感應(yīng)雷是由高壓放電在附件導(dǎo)體上的電磁感應(yīng)引起的,其強(qiáng)度雖小,但發(fā)生的概率要高得多。感應(yīng)雷電流可以通過(guò)電源線、信號(hào)傳輸線纜等的金屬部分竄入,有線電視系統(tǒng)的電子設(shè)備即使在避雷針和防雷網(wǎng)的保護(hù)下,也有可能遭到嚴(yán)重?fù)p壞。
2 雷電有線電視前端機(jī)房的主要途徑
2.1 通過(guò)供電線路侵入
有線電視前端機(jī)房基本是采用市電供電,市電接入配電室再通過(guò)UPS進(jìn)入機(jī)房。在遭受雷擊時(shí),市電線路及供電設(shè)備上有可能產(chǎn)生相當(dāng)高的感應(yīng)電壓,感應(yīng)電流將順著供電線路侵入有線電視前端機(jī)房。
2.2 通過(guò)信號(hào)傳輸線路侵入
有線電視前端機(jī)房有大量的信號(hào)傳輸線路進(jìn)出機(jī)房,當(dāng)遭遇強(qiáng)烈雷擊時(shí),信號(hào)傳輸線路上可能會(huì)產(chǎn)生高壓感應(yīng)電流。還有就是當(dāng)埋地線纜附近的地面突出物遭到雷擊時(shí),強(qiáng)大的放電電壓可能透過(guò)周圍土壤擊穿線纜外皮,繼而侵入信號(hào)傳輸線路。信號(hào)傳輸線路與前端設(shè)備直接連接,雷電電流可能循信號(hào)傳輸線路進(jìn)入而燒毀前端設(shè)備。
2.3 通過(guò)電子設(shè)備接地體侵入
當(dāng)雷電擊中避雷針時(shí),避雷針接地體對(duì)大地放電,如果在足夠近的距離內(nèi)有其它電子設(shè)備的接地體,放電產(chǎn)生的高壓地電位反擊電流將通過(guò)接地體侵入電子設(shè)備,使設(shè)備“間接”遭受雷擊。
3 有線電視前端機(jī)房防雷措施綜述
前端機(jī)房防雷工作主要分為四大部分。
3.1 供電線路防雷
據(jù)有線電視設(shè)備雷害事故統(tǒng)計(jì),約70%以上是由雷電通過(guò)供電線路侵入造成的,為此我們應(yīng)根據(jù)實(shí)際情況在以下位置加裝避雷器或其它防護(hù)裝置:(1)在供電線路上加裝避雷器,位置在供電線路進(jìn)入配電室之前。在供電線路遭雷擊時(shí),可將大部分感應(yīng)電流釋放掉。(2)在配電室安裝低壓避雷器??梢赃M(jìn)一步消釋放雷擊感應(yīng)電流。(3)如果條件允許,還可在前端機(jī)房配電柜前加裝避雷器形成三級(jí)避雷,以進(jìn)一步減弱感應(yīng)電流。剩余的電流能量在理論上已不能危害到設(shè)備安全了。
3.2 樓頂天線防雷
機(jī)房樓樓頂一般安裝有衛(wèi)星天線鍋和無(wú)線接收天線,并且附近無(wú)遮擋,高度相對(duì)較突出,易招雷襲。這些天線都通過(guò)同軸電纜與前端機(jī)房設(shè)備相連,為防止在雷擊時(shí)引入雷電電流,同時(shí)為了保護(hù)建筑物,必須加裝避雷針。為徹底防止在雷擊時(shí)從接收天線引入雷電電流,樓頂天線還需采取以下防雷措施:(1)接收天線與避雷針保持距離,至少應(yīng)大于3 m。(2)所有衛(wèi)星天線底座、無(wú)線接收天線桿和天線放大器等室外設(shè)備的金屬外殼應(yīng)連為一體并可靠接地。(3)連接樓頂衛(wèi)星接收天線和前端機(jī)房衛(wèi)星接收機(jī)的饋線等同軸電纜必須采用雙屏蔽電纜或加裝金屬護(hù)套,雙屏蔽電纜的外層或金屬護(hù)套要做到上端與天線底座連為一體,下端連接接地母線。
3.3 進(jìn)出機(jī)房線纜防雷
有線電視前端有許多信號(hào)傳輸線纜進(jìn)出機(jī)房,當(dāng)遭遇強(qiáng)烈雷擊時(shí),傳輸線纜上可能會(huì)產(chǎn)生高壓感應(yīng)電流。并由線纜的金屬部分引入機(jī)房,所以信號(hào)傳輸線纜應(yīng)做到幾點(diǎn):(1)線纜的各個(gè)出入口位置都應(yīng)在避雷針的保護(hù)范圍內(nèi)。(2)在線纜進(jìn)出前端機(jī)房時(shí)應(yīng)按照“內(nèi)高外低”的原則,以免雨水順線纜流入機(jī)房。這樣可防止雷電電流通過(guò)雨水導(dǎo)入機(jī)房,同時(shí)避免機(jī)房設(shè)備短路。(3)在信號(hào)傳輸線纜的外皮上加裝避雷器,將線纜的外皮等金屬部分引入的雷電電流釋放掉。
3.4 設(shè)備保護(hù)接地
采用市電交流電源供電的電器設(shè)備應(yīng)實(shí)施保護(hù)接地,即工作接地。有線電視前端機(jī)房的機(jī)柜、機(jī)架、電視墻、操作臺(tái)和設(shè)備的金屬外殼等要用專門的接地裝置可靠接地,以釋放掉電纜、光纜的金屬部分引入的雷電和設(shè)備漏電、靜電等。
4 有線電視前端機(jī)房防雷基本要求
4.1 供電線路防雷基本要求
(1)避雷器必須可靠接地,接地線必須用截面積大于4 mm2的絕緣導(dǎo)線,接地電阻小于4 Ω。(2)如有條件,除了供電線路的避雷接地外,還應(yīng)做好配電室供電接地、機(jī)房電源接地以及配電柜,UPS等的接地工作,其中配電室接地電阻應(yīng)小于5 Ω。(3)供電電源的零線最好做到重復(fù)接地。
4.2 采用避雷針?lè)览椎幕疽?/p>
(1)避雷針安裝方式常見(jiàn)的有兩種:一是架設(shè)避雷塔,避雷針位于鐵塔頂端,整個(gè)機(jī)房樓及樓頂天線都處在避雷塔保護(hù)范圍內(nèi);二是在機(jī)房樓的樓頂四周邊緣位置安裝多個(gè)避雷針,并且所有避雷針連為一體,圍繞整個(gè)機(jī)房樓及樓頂天線形成一個(gè)保護(hù)圈。(2)避雷針高度應(yīng)滿足對(duì)樓頂天線保護(hù)的基本要求。如安裝單根避雷針時(shí),按照避雷針保護(hù)特性,避雷針與天線高度差的數(shù)值應(yīng)大于天線最大幾何尺寸。(3)避雷針應(yīng)采用接地引下線和接地體接入大地。引下線多采用截面積大于60 mm2的鍍鋅扁鐵,連接處焊接固定,防止松動(dòng)、銹蝕增大接地電阻。接地體可采用鍍鋅角鐵、銅網(wǎng)等,埋入地下1.5 m以下,最好圍繞機(jī)房樓多點(diǎn)布設(shè)。(4)避雷接地必須與接收天線接地嚴(yán)格分開(kāi),單獨(dú)接地。且接地電阻應(yīng)小于4 Ω。
4.3 工作接地
(1)工作接地的接地引下線應(yīng)采用扁銅條以降低接地電阻,并與其它地線保持1.5 m以上距離。為避免電磁干擾還可加裝屏蔽層。(2)接地母線應(yīng)選用較寬的扁銅條,在防靜電地板下用絕緣物體支撐懸空架設(shè)。接地母線采用星型分配結(jié)構(gòu),擴(kuò)展到每一組機(jī)柜、操作臺(tái)和電視墻附近。(3)各機(jī)柜、操作臺(tái)、電視墻和防靜電地板分別與接地母線連接,連接線必須采用同等長(zhǎng)度的扁銅帶或截面積大于2.5 mm2的銅導(dǎo)線,兩端連接處采用銅螺栓緊固。切不可將機(jī)架、操作臺(tái)等串聯(lián)起來(lái)再與接地母線相連,這樣會(huì)因?yàn)榻拥仉娮璧牟煌瑢?dǎo)致較大電位差。(4)各個(gè)機(jī)柜、操作臺(tái)、電視墻等內(nèi)部的金屬部件應(yīng)連為一體,上架安裝的設(shè)備外殼應(yīng)與機(jī)柜、操作臺(tái)等內(nèi)部的金屬部件保持良好接觸。(5)工作接地的地線要單獨(dú)布設(shè),工作接地電阻應(yīng)小于4 Ω。接地體多采用面積大于1.5 m2的銅板、銅網(wǎng),在地下1.5 m以下,并與防雷接地分開(kāi)50 m以上布設(shè)。接地體附近土壤應(yīng)保持濕潤(rùn),必要時(shí)可使用降阻劑。
參考文獻(xiàn)